From Design, Engineering, Assembly to Testing of LV Switchgear, end to end carried out within SAS facility.
The SAS LV switchboard designs are in-house developed by Design team to ensure that all statutory and mandatory processes are followed, which meets all Local and International Standards.
SAS Galfar Low Voltage switchgear systems are Type Tested comprehensively meeting the IEC 61439 standards in certified European-accredited independent laboratories.
The SAS Galfar Enclosures systems are sturdy in build, yet their dynamic construction is created thoughtfully so it can adapt quickly to diverse application requirements.
Our capacity to construct complex panels with withdrawable motor control units and power switchgear that can carry large currents down to simple distribution boards that handle small loads at the consumer level; makes us a one-stop destination for all clients.
Technical Specifications
LV Switchgear / Motor Control Centers/ Distribution Boards meeting IEC 61439 Standards.
Description |
LVAC Switchgear |
Bus bar Material |
Electrolytic Grade Copper for Main and Distribution bus bars |
Enclosure |
Sheet Steel, Free standing, Floor mountable type. |
Construction |
Up to Form 4B type Up to IP 54 |
Shade /Thickness |
Our standard RAL7032 (exterior) , RAL9003(interior). Other color shades on request |
Cable Entry |
As per site requirement |
Terminal Blocks |
Disconnecting type for CT , VT secondary Circuits, Non Disconnecting types for AC/ DC and Control Circuits Knife edge terminals for Alarm and SCADA circuits |
CT/VT/Control Wiring |
PVC Insulated , Stranded Copper Conductors , Tri Rated , 600/1000 V Grade, Flame Retardant Low Smoke type meeting BS 6231, CT & VT Secondary Circuits – 2.5 sq mm, R,Y,B & Black. DC Circuits – 1.5 sq mm Grey, AC Circuits – 1.5 sq mm Black, Heater & Illumination – 2.5 sq mm Black, Protective Earth – 2.5 sq mm Y/G, Other Colors on request. |
Control wire markers |
White PVC tubes with Indelible marking as per client practice. |
Labels |
PVC / Traffolyte Engraved Labels with Black lettering on White background of different sizes |
Mimic |
Mimic shall be PVC, Sticker type with good adhesive properties |
Design Features
- • Up to 1000 V AC & 1500 V DC.
- • Designed as per IEC 62208 standards with galvanized sheet metal
- • Resistance to corrosion—IEC 60068-2-30 (test Db) at (40+/-3 deg C) and RM 95%.
- • Design verification tests done at DEKRA, KEMA& UL.
Electrical tests as per IEC 61439
- LV Panels are designed according to IEC 62262, IEC 62208 for IK10 Impact and Internal Arc.
- Conforming to Severity Class A for indoor and Severity Class B for outdoor.
- Available in draw-out and non-draw out versions
- Available in Form 4b and Form 2b construction with up to IP54 ingress protection